Technical parameters:
Raw water hardness: ≤ 8 mmol/L
Working environment temperature: 5 ℃-50 ℃
Water hardness: ≤ 0.03mmol/L
Relative temperature: ≤ 95%(25 ℃)
Inlet water pressure: 0.2 Mpa-0.5Mpa
Power supply: 220V ± 22V/50Hz
Water temperature: 5 ℃-45 ℃
Resin type: strong acid cation exchange resin
Free chlorine: ≤ 0.3mg/L
Regeneration control: downstream timing type, quantitative type
Suspended solids:<5mg/L
Interface type: thread or ABS flange
Iron content:<0.3mg/L
Selection description:
Select the equipment model according to the actual water conditions
When the hardness of raw water is ≤ 6mmol/L, it can be selected according to the large water yield listed in the table.
When the hardness of raw water is less than or equal to 8mmol/L, it can be selected according to the small water yield listed in the table.
When the original small hardness is less than or equal to 8mmol/L, secondary softening is recommended.
When the regularity of water use is strong, time control can be used.
When the water is irregular and the raw water is poor, the flow control method is used.
Time flow control mode can also be adopted at the same time, that is, when the amount of softened water reaches the set time, the regeneration user needs to increase the number of regeneration in the state of over-quantitative water use, the controller with manual function can be selected.